Client: A large data center from a mobile operator
Condition: The power distribution system of
the data center, especially in the server room and the network room, contains a
lot of UPS, cooling equipment and other power electronic devices such as
switching power supplies. These devices create disturbances, voltage variations
and undesired harmonics that pollute the network. This harmonic pollution could
then interfere with the communication signals in various ways, thus affecting the
quality of communication.
Designed power supply: A 10 kV feeding line
is connected with a transformer with a capacity of 2000 kVA, voltage ratio
10/0.4 kV. The main loads are the various types of communications and storage
devices in the network which are located in the server room and network room.
Main problem: The harmonic voltage,
harmonic current and power factor low-voltage side of the transformer are
measured. The THDv reaches 5.1%, which exceeds the national rate of 5%. The
THDi reaches an astonishing rate of 26% and has an RMS value of 490 A. Thanks
to the use of the latest generation of UPS power, the power factor can be as
high as 0.82, but still does not meet the national requirement.
Compensation design: Considering the fact
that the actual harmonic could have a certain range of fluctuation, the
configuration needs to have a certain margin to deal with possible changes.
Therefore the proposed MSAF should have a rated current of 530A. The test results
also shows that the three-phased system is unbalanced and the zero sequence
harmonic current in neutral conductor is too large. The active filter applied
should have a star connection with neural line and our MSAF-M-690/560-WO is
recommended.